KRUN-E-6 in the K-VI-U frame: switchgear designed to stand in the open
Outdoor 6 kV switchgear cubicles: an incomer rated 1250 A and a feeder rated 630 A. Location category 1 — service in the open with no building, from −25 to +40 °C. The degree of protection changes with the doors: IP54 closed, IP20 with the outer doors open. Built at our own plant in Odesa, 2025. ---
The task
6 kV switchgear has to go somewhere. The classic route is to build it a room: walls, roof, doors, heating, ventilation. That is money, lead time and approvals before the first cubicle even reaches the site.
The alternative is equipment that is its own building: outdoor-rated cubicles. But the demands on them are tougher than on indoor gear, and not only in terms of sealing:
- Weather. Rain, snow, frost, heat and condensation work on the insulation and the contacts all year round, not just during a fault.
- Operator safety while working. When an operator opens the outer doors in the rain, protection against contact with live parts must not disappear.
- Access. A cubicle standing in a row in the open has to be reachable from both front and back, otherwise inspecting the busbars turns into a dismantling job.
The solution
We built KRUN-E series cubicles for 6 kV in the K-VI-U frame: an incomer rated 1250 A (serial no. 174039) and a feeder rated 630 A (serial no. 174040). Both carry their own factory passports.
Figures (from the passports)
| Serial number | 174039 | 174040 |
| Frame | K-VI-U | K-VI-U |
| Rated voltage | 6 kV | 6 kV |
| Highest working voltage | 7.2 kV | 7.2 kV |
| Frequency | 50 Hz | 50 Hz |
| Rated current, main circuits | 1250 A | 630 A |
| Rated breaking current | 25 kA | 25 kA |
| Dynamic withstand | 50 kA | 50 kA |
| Thermal withstand | 25 kA (3 s) | 25 kA (3 s) |
| Auxiliary circuit voltage | 220 V | 220 V |
| Degree of protection | IP54 / IP20 / IP00 | IP54 / IP20 / IP00 |
| Dimensions (H×W×D) | 2500 × 1000 × 1900 mm | 2500 × 1000 × 1900 mm |
| Weight, max | 1000 kg | 1000 kg |
| Climatic design | U, category 1 | U, category 1 |
| Operating temperature | −25 to +40 °C | −25 to +40 °C |
| Technical specification | TU U 27.1-40132794-002:2016 | TU U 27.1-40132794-002:2016 |
Dimensions are given without the overhead entry.
The series product card: Outdoor packaged switchgear (KRUN-E). For design engineers: the standard solution Typical solution: KRUN 10 kV. A related case: KRU-E in the KM-1F frame — 16 cubicles at 6 kV.
Photo report from production

We will build to your diagram
Do you need 6–10 kV switchgear without building a room for it? Send us a single-line diagram and our engineer will select the cubicle frame, the ratings and the lead time. Preliminary quotation within 24 working hours.
Need a similar project?
We’ll estimate yours
Send us your specification or describe the task — we will propose a solution and estimate the time and cost. Preliminary reply within 24 hours.
+380 67 104 94 91