Home/Projects/KRUN-E-6 in the K-VI-U frame: switchgear designed to stand in the open

KRUN-E-6 in the K-VI-U frame: switchgear designed to stand in the open

Outdoor 6 kV switchgear cubicles: an incomer rated 1250 A and a feeder rated 630 A. Location category 1 — service in the open with no building, from −25 to +40 °C. The degree of protection changes with the doors: IP54 closed, IP20 with the outer doors open. Built at our own plant in Odesa, 2025. ---

KRUN-E-6 in the K-VI-U frame: switchgear designed to stand in the open

The task

6 kV switchgear has to go somewhere. The classic route is to build it a room: walls, roof, doors, heating, ventilation. That is money, lead time and approvals before the first cubicle even reaches the site.

The alternative is equipment that is its own building: outdoor-rated cubicles. But the demands on them are tougher than on indoor gear, and not only in terms of sealing:

  • Weather. Rain, snow, frost, heat and condensation work on the insulation and the contacts all year round, not just during a fault.
  • Operator safety while working. When an operator opens the outer doors in the rain, protection against contact with live parts must not disappear.
  • Access. A cubicle standing in a row in the open has to be reachable from both front and back, otherwise inspecting the busbars turns into a dismantling job.

The solution

We built KRUN-E series cubicles for 6 kV in the K-VI-U frame: an incomer rated 1250 A (serial no. 174039) and a feeder rated 630 A (serial no. 174040). Both carry their own factory passports.

Figures (from the passports)

Serial number174039174040
FrameK-VI-UK-VI-U
Rated voltage6 kV6 kV
Highest working voltage7.2 kV7.2 kV
Frequency50 Hz50 Hz
Rated current, main circuits1250 A630 A
Rated breaking current25 kA25 kA
Dynamic withstand50 kA50 kA
Thermal withstand25 kA (3 s)25 kA (3 s)
Auxiliary circuit voltage220 V220 V
Degree of protectionIP54 / IP20 / IP00IP54 / IP20 / IP00
Dimensions (H×W×D)2500 × 1000 × 1900 mm2500 × 1000 × 1900 mm
Weight, max1000 kg1000 kg
Climatic designU, category 1U, category 1
Operating temperature−25 to +40 °C−25 to +40 °C
Technical specificationTU U 27.1-40132794-002:2016TU U 27.1-40132794-002:2016

Dimensions are given without the overhead entry.

The series product card: Outdoor packaged switchgear (KRUN-E). For design engineers: the standard solution Typical solution: KRUN 10 kV. A related case: KRU-E in the KM-1F frame — 16 cubicles at 6 kV.

Photo report from production

A KRUN-E-6 cubicle in the K-VI-U frame with its doors closed — the IP54 operating state Two-tier cubicle construction: relay compartment above, switching compartment below Relay compartment of the cubicle: instruments, indicator gear and control switches The cubicle with the doors of both tiers open Circuit breaker in the lower compartment of the KRUN-E-6 cubicle Lower compartment of the cubicle with its ventilation louvre Upper compartment: main-circuit bushings The cubicle from the rear: access to busbars and connections from the second side Outer doors of the outdoor cubicle standing open Factory nameplate: 6 kV, 1250 A, IP54, 1000 kg, serial number 174039

We will build to your diagram

Do you need 6–10 kV switchgear without building a room for it? Send us a single-line diagram and our engineer will select the cubicle frame, the ratings and the lead time. Preliminary quotation within 24 working hours.

Need a similar project?
We’ll estimate yours

Send us your specification or describe the task — we will propose a solution and estimate the time and cost. Preliminary reply within 24 hours.

+380 67 104 94 91
Discuss the project

Send your single-line diagram or specification to info@lk-energy.com.ua — or we will contact you and ask.

+380 67 104 94 91you can copy the numberLeave your number — we’ll call back →
+38 067 104-94-91