Standard solution: protective enclosure (steel box) and foundation for a DG
Standard solution for the outdoor installation package of a standby diesel generator: steel box, monolithic reinforced-concrete foundation, exhaust gas outlet and earthing loop. PDFs are open access.
Solution files
1 PDF · 573 KB — open access- DGU enclosure and foundation: box, foundation, exhaust outlet, earthing, cable sealingPDF · 573 KBdrawing5 sh.
There is no DWG for this solution yet — PDFs are available.
Published: 18.07.2026 · Author: engineering department, LK Energy Group


A standard solution for outdoor installation of a standby diesel generator (DG): protective steel enclosure (box), monolithic reinforced-concrete foundation, exhaust gas outlet assembly and earthing loop. The solution is based on a real 2021–2026 standby power project where the DG is installed in the open air and is brought into operation automatically by a mains–generator ATS panel. The PDF is freely available.
When a separate enclosure and foundation are needed for a DG
The factory weatherproof canopy protects the unit itself from precipitation, but stationary installation of a generator on a site requires three more things that are usually not included in the DG supply: a foundation that carries the weight of the unit and the dynamic loads from its operation, an organized exhaust outlet above the enclosure roof, and an earthing loop. These are exactly the elements covered by this standard solution — a steel box over the unit, a reinforced-concrete slab under it, an exhaust pipe with a roof penetration, and an earthing arrangement. The solution gives the design engineer a ready basis for the civil and electrical parts of the DG site.
Composition and technical parameters
- Steel enclosure (box) with approximate dimensions of 4500×2500×2000 mm: welded frame, removable roof, intake and exhaust ventilation louvres
- Monolithic reinforced-concrete foundation — slab of concrete class B25, frost resistance F150, water resistance W2
- Slab reinforcement: Ø12 rebar, grade A500C; reinforcement specification per project — approximately 280 kg
- Exhaust gas outlet: DN76 pipe, rain cap, roof penetration via a MasterFlash roof seal
- Earthing loop for the enclosure and the DG
- The DG is installed outdoors and operates automatically; the mains–generator transfer is performed by a separate ATS panel (see the standard 0.4 kV ATS solution)
- Developed from real projects of 2021–2026
- The box dimensions, foundation class and reinforcement are given per a specific project and are adjusted to the weight and dimensions of the selected generator model
We manufacture the equipment at our own facility in Odesa; see also the equipment catalog.
FAQ
Why a separate enclosure if the generator already has a factory canopy?
The factory canopy protects the unit from the weather, but it does not replace a foundation for the generator weight, an organized exhaust outlet above the roof, or an earthing loop. This standard solution covers exactly the civil and utility part of an outdoor DG site.
Does it include selection of the diesel generator itself?
No. The box and foundation are designed for a specific DG model — its dimensions, weight and exhaust parameters are defined by the design engineer. The solution is provided as a standard basis to be adapted to the selected unit.
Does LK Energy Group manufacture steel enclosures for DGs?
Yes — we manufacture steel boxes, ATS panels and related switchboard equipment at our own facility in Odesa.
We advise design engineers on the equipment configuration: +38 067 104 94 91.
This is a reference standard solution. Site-specific adaptation, load and setting calculations, and compliance with the applicable codes (PUE, DSTU, DBN) are the responsibility of the design engineer. LK Energy Group accepts no liability for use of the solution without adaptation to the conditions of a specific site.
Any questions left?
Write or call us — we answer to the point. Preliminary reply within 24 hours.
+380 67 104 94 91