General information
Incoming-distribution devices VRP, UVR (ВРП, УВР) are designed (depending on panel type) for receiving, distributing and metering three-phase AC electric power with a voltage of 380/220 V, frequency 50 Hz, with a solidly earthed neutral, as well as for protecting lines against overloads and short-circuit currents.
The devices are designed for installation in electrical switchgear rooms. Wire and cable entry/exit is provided from below. The devices are manufactured for single-sided (front) access and are intended for operation in residential, communal-domestic and public buildings. Use of the devices at other facilities with a similar power supply scheme is permitted.
The VRP switching apparatus is of air-type and moulded-case design (switch-disconnectors, ПН-2/ППН fuses, MCCB/ACB circuit breakers, current transformers). The specific composition and ratings are selected for the project as per the technical specification (TS).
- Rated operating mode — continuous.
- Climatic design — U3.
- Degree of protection — IP30, IP00 from the bottom side.
- Busbar (rated) current — generally up to 1000 A (per project).
The devices comply with DSTU EN 61439-1, DSTU IEC 60439-1 and the manufacturer's own technical specifications (TU). VRP units are manufactured to order per the technical specification; ratings, apparatus set and panel layout are determined by the project.
Main technical characteristics (typical panel designs)
| Panel type | Rated current, A | Current transformers T-0.66 | Outgoing lines (CB), A | Lighting control | Diagram (Fig. No.) | |||
|---|---|---|---|---|---|---|---|---|
| Ratio | Qty | 63 | 100 | 250 | ||||
| Incoming panels | ||||||||
| PVR 1201 | 250 | 300/5 | 6 | — | 1 | |||
| PVR 1202 | 250 | 200/5 | 6 | — | 3 | |||
| PVR 1203 | 250 | 200/5; 100/5 | 3; 3 | — | 1 | |||
| PVR 1401 | 400 | 400/5 | 6 | — | 1 | |||
| PVR 1402 | 400 | 400/5; 300/5 | 3; 3 | — | 3 | |||
| PVR 1403 | 400 | 400/5; 100/5 | 3; 3 | — | 1 | |||
| VRP-1-11-10 | 250 | 300/5 | 6 | — | 1 | |||
| VRP-1-12-10 | 250 | 300/5 | 3 | — | 2 | |||
| VRP-1-13-20 | 400 | 400/5 | 6 | — | 1 | |||
| VRP-1-14-20 | 400 | 400/5 | 3 | — | 2 | |||
| VRP-1-17-70 | 100 | 100/5 | 3 | — | 4 | |||
| VRP-1-18-80 | 250 | 200/5 | 3 | — | 4 | |||
| Incoming-distribution panels | ||||||||
| PVR 2201 | 250 | 300/5 | 3 | 8 | 6 | Automatic | 5 | |
| PVR 2202 | 250 | 300/5; 100/5 | 3; 3 | 8 | 6 | Automatic | 6 | |
| PVR 2203 | 250 | 300/5 | 3 | 8 | 6 | Automatic | 7 | |
| PVR 2204 | 250 | 300/5; 100/5 | 3; 3 | 8 | 6 | Automatic | 8 | |
| VRP-1-21-10 | 200 | 200/5 | 3 | 2 | 4 | None | 9 | |
| VRP-1-22-53 | 200 | 14 | 5 | Automatic | 10 | |||
| VRP-1-22-54 | 200 | 14 | 5 | Manual | 11 | |||
| VRP-1-22-55 | 200 | 8 | 5 | Automatic | 12 | |||
| VRP-1-22-56 | 200 | 8 | 5 | Manual | 13 | |||
| VRP-1-23-53 | 200 | 200/5 | 3 | 14 | 5 | Automatic | 14 | |
| VRP-1-23-54 | 200 | 200/5 | 3 | 14 | 5 | Manual | 15 | |
| VRP-1-23-55 | 200 | 200/5 | 3 | 8 | 5 | Automatic | 16 | |
| VRP-1-23-56 | 200 | 200/5 | 3 | 8 | 4 | 1 | Manual | 17 |
| VRP-1-24-53 | 200 | 100/5 | 3 | 14 | 5 | Automatic | 18 | |
| VRP-1-24-54 | 200 | 100/5 | 3 | 14 | 5 | Manual | 19 | |
| VRP-1-24-55 | 200 | 100/5 | 3 | 8 | 5 | Automatic | 20 | |
| VRP-1-24-56 | 200 | 100/5 | 3 | 8 | 4 | 1 | Manual | 21 |
| VRP-1-25-63 | 200 | 14 | 5 | Automatic | 22 | |||
| VRP-1-25-64 | 200 | 14 | 4 | 1 | Manual | 23 | ||
| VRP-1-25-65 | 200 | 8 | 4 | 1 | Automatic | 24 | ||
| VRP-1-25-66 | 200 | 100/5 | 3 | 8 | 4 | 1 | Manual | 25 |
| VRP-1-26-63 | 200 | 200/5 | 3 | 14 | 5 | Automatic | 26 | |
| VRP-1-26-64 | 200 | 200/5 | 3 | 14 | 4 | 1 | Manual | 27 |
| VRP-1-26-65 | 200 | 200/5 | 3 | 4 | 1 | None | 28 | |
| VRP-1-26-66 | 200 | 8 | 4 | 1 | Manual | 29 | ||
| VRP-1-27-63 | 200 | 100/5 | 3 | 14 | 5 | Automatic | 30 | |
| VRP-1-27-64 | 200 | 100/5 | 3 | 14 | 4 | 1 | Manual | 31 |
| VRP-1-27-65 | 200 | 100/5 | 3 | 8 | 4 | 1 | Automatic | 32 |
| VRP-1-27-66 | 200 | 100/5 | 3 | 8 | 4 | 1 | Manual | 33 |
| VRP-1-28-63 | 200 | 100/5 | 3 | 14 | 5 | Automatic | 34 | |
| VRP-1-28-64 | 200 | 200/5 | 3 | 14 | 4 | 1 | Manual | 35 |
| VRP-1-28-65 | 200 | 100/5 | 3 | 8 | 4 | 1 | Automatic | 36 |
| VRP-1-28-66 | 200 | 200/5 | 3 | 14 | 4 | 1 | Manual | 37 |
| VRP-1-29-63 | 200 | 200/5 | 6 | 14 | 5 | Automatic | 38 | |
| VRP-1-29-64 | 200 | 200/5 | 6 | 14 | 4 | 1 | Manual | 39 |
| VRP-1-29-65 | 200 | 200/5 | 6 | 8 | 4 | 1 | Automatic | 40 |
| VRP-1-29-66 | 200 | 200/5 | 6 | 8 | 5 | Manual | 45 | |
| Distribution panels | ||||||||
| PVR 3001 | 200 | 30 | 5+2 | 2 | Manual | 41 | ||
| PVR 3002 | 200 | 30 | 5+2 | 2 | Automatic | 42 | ||
| PVR 3003 | 200 | 30 | 5+5 | Manual | 43 | |||
| PVR 3004 | 200 | 30 | 5+5 | Automatic | 44 | |||
| VRP-1-41-00 | 200 | 7+2 | None | 46 | ||||
| VRP-1-42-01 | 200 | 30 | 7+2 | Automatic | — | |||
| VRP-1-42-01 | 200 | 30 | 7+2 | Manual | — | |||
| VRP-1-43-00 | 200 | 300/5 | 3 | 7+2 | None | 47 | ||
| VRP-1-44-00 | 200 | 7 | 2 | None | — | |||
| VRP-1-45-01 | 200 | 30 | 7 | 2 | Automatic | — | ||
| VRP-1-45-02 | 200 | 30 | 7 | 2 | Manual | — | ||
| VRP-1-46-00 | 200 | 300/5 | 3 | 7 | 2 | None | 47 | |
| VRP-1-47-00 | 200 | 5+5 | None | 48 | ||||
| VRP-1-48-03 | 200 | 14 | 5+5 | Automatic | 49 | |||
| VRP-1-48-04 | 200 | 16 | 5+5 | Manual | 50 | |||
| VRP-1-49-00 | 200 | 5+5 | None | 48 | ||||
| VRP-1-49-03 | 200 | 14 | 5+5 | Automatic | 49 | |||
| VRP-1-49-04 | 200 | 16 | 5+5 | Manual | 50 | |||
| VRP-1-50-00 | 400 | 4+4 | None | — | ||||
| VRP-1-50-01 | 400 | 30 | 4+4 | Automatic | 51 | |||
| VRP-1-50-02 | 400 | 30 | 4+4 | Manual | 52 | |||
The designs shown are typical; the apparatus composition and ratings are refined per project as per the technical specification. Manufacturer — LK Energy Group, Odesa.
Dimensions

Diagram grid
Show all images (15)















RPNN cabinet design






Description and purpose
An incoming distribution switchboard (VRP/UVR) is a low-voltage 0.4 kV (380/220 V, 50 Hz) switchgear assembly for receiving, distributing and metering electricity at the point of entry into a building or facility, with protection of the lines against overloads and short circuits. The assembly's rated current varies depending on the configuration, typically up to 1000 A. Ratings, the set of apparatus (disconnect switches, PN-2/PPN fuses, circuit breakers, current transformers, metering unit) and the panel layout are engineered to your project specification. LK Energy Group is an Odesa-based manufacturer of switchgear equipment, in business since 2005: we design and build VRPs for your specific task, with a warranty and compliance with current standards.
FAQ
What is a VRP/UVR and which facilities is it designed for?
What current is the VRP rated for?
Is it a standard design or built to project specification?
Can incoming supply, metering and distribution be combined in a single VRP?
What standards does LK Energy equipment comply with?