Home/Equipment/Incoming Metering Boxes (IMB / YaVU)

Incoming Metering Boxes (IMB / YaVU)

General information

Purpose of YaVU

An electricity meter box — an incoming metering box (IMB, Ukr. ЯВУ) — is an enclosure for the electricity meter with an incoming circuit breaker and protection of outgoing feeders at 0.4 kV (400 V, 50 Hz). It is installed at the supply intake when the distribution system operator (DSO) requires a separate, sealable metering point. We build three-phase YaVU-3 units to your technical conditions — for indoor and outdoor installation. For outdoor installation an IP54 version is used; below −25 °C the metering compartment is fitted with heating — an option, not part of the base version.

Input-metering boxes YaVU (ЯВУ) are complete low-voltage distribution devices designed for input reception, commercial metering, and protection of outgoing lines in 0.4 kV (400 V) three-phase AC networks with a frequency of 50 Hz and a solidly grounded neutral. YaVU units are installed at the power supply input of industrial, utility and public facilities.

Structurally, the box is a front-access enclosure made of metal (powder-coated steel) or modified plastic (PC/ABS). Inside are located: an input circuit breaker, a space for an electricity meter (direct or transformer connection), distribution circuit breakers on the outgoing lines, PEN/N/PE terminals, and sealing lugs for the metering compartment.

Standards and types

  • DSTU EN 61439-1:2014 — Low-voltage switchgear and controlgear assemblies. Part 1. General rules.
  • DSTU EN 61439-3:2014 — Part 3. Distribution boards intended to be operated by ordinary persons.
  • DSTU EN 60529:2018 — Degrees of protection provided by enclosures (IP code).
  • Manufacturer's own technical specifications.

An incoming metering box is not only a wall box: delivered work includes floor-standing metering cabinets at 250, 600 and 630 A.

LK Energy Group has been manufacturing switchgear equipment at its own factory in Odesa since 2015 (company since 2005). We have been producing the YaVU line since 2015; these are three-phase YaVU-3 boxes for 400 V — from wall-mounted versions to floor-standing metering cabinets. Designs: for enterprises, utility and public facilities, developers. Degree of protection — IP31 for indoor premises and IP54 for outdoor installation.

Typical electrical circuit of YaVU

The basic design of YaVU-3 with direct meter connection consists of:

QF1
input circuit breaker (three poles for YaVU-3, rating — project-specific based on calculated current);
PI
three-phase electronic active energy meter (direct or transformer connection via CT);
QF2…QFn
circuit breakers on the outgoing lines (quantity and ratings — per technical specification);
XT
PEN/N/PE terminal set with a sealing lug on the metering compartment.

For transformer connection, the circuit additionally includes three current transformers (CT) with ratios of 100/5, 200/5, 400/5, 600/5, or 1000/5 — depending on the calculated current. A detailed schematic diagram for the specific design is included with the product's data sheet.

Main parameters of YaVU

Parameter nameValue
Rated voltage, V400 (3-ph), AC
Frequency, Hz50
Grounding systemTN-C-S (solidly grounded neutral)
Rated currentproject-specific (direct or transformer connection via CT)
Degree of protection (indoor)IP31 per DSTU EN 60529:2018
Degree of protection (outdoor)IP54 per DSTU EN 60529:2018
Enclosure materialPowder-coated steel / PC-ABS plastic
Climatic design (outdoor)operating range −40…+40 °C; below −25 °C — with heating of the metering compartment
Climatic design (indoor)UKhL4, -10…+40 °C
Mounting typeWall-mounted / built-in / pole-mounted
Dimensions (H×W×D), mmwall-mounted versions — up to 500×600×200*; floor-standing metering cabinets — up to 2000×600×400 (+ 200 base)
Weight, kgwall-mounted versions — up to 15*; floor-standing metering cabinets — up to 80 (YaVU 600 A per passport)
Operating modecontinuous
StandardsDSTU EN 61439-1/-3:2014

*For IP54, the rated current is reduced relative to the values for IP31 — due to limited heat dissipation through the closed enclosure. The exact value is project-specific.

*Approximate dimensions, weight, and configuration. Final parameters are agreed upon at the inquiry sheet stage. Custom designs — per the Customer's technical specification.

Standard configuration of YaVU

  • input circuit breaker for the calculated current;
  • space for an electricity meter with direct or transformer connection (DIN rail or mounting panel);
  • circuit breakers on the outgoing lines;
  • PEN/N/PE terminal block with a sealing lug;
  • set of sealing lugs for the metering compartment;
  • mounting loops / brackets for wall mounting.

Options on request

  • current transformers (CT) 100/5…1000/5 for indirect meter connection;
  • surge protection devices (SPD) class I+II;
  • 230 V service outlet in a separate compartment;
  • heating of the metering compartment for outdoor installation (below -25 °C);
  • LED compartment lighting with door switch;
  • enclosure color — RAL 7035 (light gray) standard, other RAL colors — on request.

Electricity meters

The box is supplied without a meter. The model is determined by the technical conditions of your DSO (Oblenergo). All installed meters must be certified in Ukraine and included in the DSO's register.

Lead time and warranty

Typical manufacturing time — 5–7 business days for standard models, up to 14 days for custom designs*. Warranty — 2 years from the date of commissioning (extended to 5 years by agreement); enclosure metalwork — 10 years*.

*Approximate lead times and conditions. Exact lead time and warranty — as specified in the supply agreement.

Electrical diagram

Typical electrical diagram of YaVU (Ukr. ЯВУ):

Electrical diagram of YaVU

The diagram is shown for the basic design of YaVU-3 with direct-connected metering. Composition:

QF1
input automatic circuit breaker (three poles for YaVU-3, rating selected according to the calculated current)
PI
three-phase electronic active energy meter (direct-connected up to 100 A or transformer-connected via CT)
QF2…QFn
automatic circuit breakers on the outgoing lines (quantity and ratings — per technical specification)
XT
PEN/N/PE terminal block with a sealing lug on the metering compartment

For transformer connection, the circuit additionally includes three current transformers (CT) with ratios of 100/5, 200/5, 400/5, 600/5, or 1000/5 — depending on the calculated current. A detailed schematic diagram for the specific design is included with the product's data sheet.

Technical specifications

Main parameters of YaVU (ЯВУ):

Parameter nameValue
Rated voltage, V400 (3-ph), AC
Frequency, Hz50
Grounding systemTN-C, TN-C-S (solidly grounded neutral)
Rated current of the assembly, Ato project — set by the incoming breaker and enclosure
Direct meter connection, Aup to 100
Metering via CTs, primary current, A100…1000 (CTs 100/5…1000/5)
Degree of protection (indoor)IP31 per DSTU EN 60529:2018
Degree of protection (outdoor)IP54 per DSTU EN 60529:2018
Enclosure materialPowder-coated steel / PC-ABS plastic
Climatic design (outdoor)operating range −40…+40 °C; below −25 °C — with heating of the metering compartment
Climatic design (indoor)UKhL4, -10…+40 °C
Mounting typeWall-mounted / built-in / pole-mounted
Dimensions (H×W×D), mmwall-mounted versions — up to 500×600×200*; floor-standing metering cabinets — up to 2000×600×400 (+ 200 base)
Weight, kgwall-mounted versions — up to 15*; floor-standing metering cabinets — up to 80 (YaVU 600 A per passport)
Operating modecontinuous
StandardsDSTU EN 61439-1/-3:2014
Delivered units — metering cabinetsYaVU-A-250 (250 A, 2000×600×400 + 200 base); YaVU-2-250-200 U3 (250 A); YaVU 600 A, IP54, 1600×600×400, 80 kg; YaVU-630 U3 (630 A)
Short-circuit withstand (Icw / Ipk)agreed per project

*For IP54, the rated current is reduced by 15% relative to the values specified for IP31, due to limited heat dissipation through the closed enclosure.

*Approximate dimensions, weight, and configuration. Final parameters are agreed upon at the inquiry sheet stage. Custom designs — per the Customer's technical specification.

Versions and configuration

Standard configuration of the YaVU (ЯВУ)

  • incoming circuit breaker rated for the design current;
  • space for a direct-connected or CT-connected electricity meter (DIN rail or mounting panel);
  • circuit breakers on the outgoing lines;
  • PEN/N/PE terminal block with a sealing lug;
  • set of sealing lugs for the metering compartment;
  • mounting loops / brackets for wall-mounted installation.

Options on order:

  • current transformers (CT) 100/5…1000/5 for indirect meter connection;
  • surge protection devices (SPD) class I+II;
  • 230 V service outlet in a separate compartment;
  • heating of the metering compartment for outdoor installation (-45…-25 °C);
  • LED compartment lighting with a door switch;
  • enclosure colour — RAL 7035 (light grey) standard, other RAL colours — on order.

Electricity meters:

The enclosure is supplied without a meter. The model is determined by the technical requirements of your DSO (regional power distribution company, Oblenergo). All installed meters must be certified in Ukraine and listed in the DSO register.

Lead time and warranty:

Typical manufacturing lead time — 5-7 working days for standard models, up to 14 days for custom designs*. Warranty — 2 years from the date of commissioning (extended to 5 years by agreement); enclosure metalwork — 10 years*.

*Approximate lead times and terms. The exact lead time and warranty are specified in the supply agreement.

Description and purpose

An electricity meter box — a 0.4 kV metering panel (IMB / YaVU) — is a complete low-voltage assembly (400 V, 50 Hz) for accepting the supply from the DSO, commercial metering and protection of outgoing feeders. The rated current follows the calculated intake current: direct meter connection up to 100 A, above that via current transformers with ratios 100/5…1000/5. LK Energy Group — a switchgear manufacturer from Odesa, in business since 2005, with its own factory since 2015: every unit ships with a data sheet and a test report; a certificate of conformity is issued at the customer's request. The rated current and design are selected per project based on the calculated current (direct meter connection up to 100 A, above that via current transformers 100/5…1000/5). Typical example: IMB-3, incoming breaker + 3-phase meter + feeder breakers. Heating for the metering compartment is added on request — for outdoor installation in cold regions. Technical data sheet (PDF) ↓ Inquiry form for sizing →

Technical data sheet (PDF) ↓Inquiry form for sizing →

Five questions

Find the right equipment for your site

Answer them and we will come back with a configuration and a ballpark price for your site.

Question 1 of 5
What do you need?
Questions & answers

FAQ

What is the rated current of the IMB?
The rated current is selected per project based on the calculated incoming current. For direct meter connection, the devices are installed directly in the power circuit; for larger loads we use transformer connection via current transformers (CTs, 100/5…1000/5). The exact rating of the incoming breaker and the CTs is determined from your technical specification and the DSO's requirements.
Can the IMB be installed on a facade / outdoors?
Yes. For outdoor and facade installation, an IP54 design per DSTU EN 60529:2018 (Ukrainian national standard, harmonized with IEC/EN) is ordered — protection against dust and water splashes from any direction. IP54 is not a hermetically sealed enclosure, so at this protection rating the rated current is derated with a margin for heat dissipation.
Is heating provided in the IMB?
Heating is an option, not a standard feature. A heating element is added to the metering compartment on request: for outdoor installation in cold regions (below -25 °C) or when required by the devices in the configuration. Without such a requirement, the IMB is supplied without heating.
Is the meter included in the package?
No. The box is supplied with a mounting space for the meter (DIN rail or panel) and sealing lugs, but without the meter itself. The model is determined by the technical conditions of your DSO (regional grid operator); the meter must be certified in Ukraine and listed in the DSO's register.
What documentation do you issue for the IMB?
Every IMB leaves the factory with a product data sheet, an acceptance test report and installation instructions; a certificate of conformity (DSTU EN 61439-3:2014, Ukrainian national standard, harmonized with IEC/EN) is issued at the customer's request. Manufacturer's technical conditions — our own. Warranty — 2 years (extended to 5 years by agreement); enclosure metalwork — 10 years.

Price request:
Incoming Metering Boxes (IMB / YaVU)

Send us your single-line diagram or specification — we will estimate the configuration, lead time and price. Preliminary estimate within 24 business hours.

+380 67 104 94 91
Request a quote