Home/Equipment/Incoming Metering Boxes (IMB)

Incoming Metering Boxes (IMB)

General information

Purpose of YaVU

Input-metering boxes YaVU (ЯВУ) are complete low-voltage distribution devices designed for input reception, commercial metering, and protection of outgoing lines in 0.4 kV (230/400 V) three-phase or single-phase AC networks with a frequency of 50 Hz and a solidly grounded neutral. YaVU units are installed at the power supply input of industrial, public, communal-residential, and housing facilities.

Structurally, the box is a front-access enclosure made of metal (powder-coated steel) or modified plastic (PC/ABS). Inside are located: an input circuit breaker, a space for an electricity meter (direct or transformer connection), distribution circuit breakers on the outgoing lines, PEN/N/PE terminals, and sealing lugs for the metering compartment.

Standards and types

  • DSTU EN 61439-1:2014 — Low-voltage switchgear and controlgear assemblies. Part 1. General rules.
  • DSTU EN 61439-3:2014 — Part 3. Distribution boards intended to be operated by ordinary persons.
  • DSTU EN 60529:2018 — Degrees of protection provided by enclosures (IP code).
  • TU U 27.1-40132794-003:2016 — manufacturer's technical specifications.

LK Energy Group has been manufacturing switchgear equipment in Odesa since 2005. We have been producing the YaVU line since 2015; it has two main types: YaVU-1 (single-phase, 230 V) and YaVU-3 (three-phase, 400 V). Designs: for utility needs, private consumers, public and industrial facilities. Degree of protection — IP31 for indoor premises and IP54 for outdoor installation.

Typical electrical circuit of YaVU

The basic design of YaVU-3 with direct meter connection consists of:

QF1
input circuit breaker (three poles for YaVU-3, rating — project-specific based on calculated current);
PI
electronic active energy meter (1-phase or 3-phase, direct or transformer connection via CT);
QF2…QFn
circuit breakers on the outgoing lines (quantity and ratings — per technical specification);
XT
PEN/N/PE terminal set with a sealing lug on the metering compartment.

For transformer connection, the circuit additionally includes three current transformers (CT) with ratios of 100/5, 200/5, 400/5, 600/5, or 1000/5 — depending on the calculated current. A detailed schematic diagram for the specific design is included with the product's data sheet.

Main parameters of YaVU

Parameter nameValue
Rated voltage, V230 (1-ph) / 400 (3-ph), AC
Frequency, Hz50
Grounding systemTN-C-S (solidly grounded neutral)
Rated currentproject-specific (direct or transformer connection via CT)
Degree of protection (indoor)IP31 per DSTU EN 60529:2018
Degree of protection (outdoor)IP54 per DSTU EN 60529:2018
Enclosure materialPowder-coated steel / PC-ABS plastic
Climatic design (outdoor)UKhL2, -25…+40 °C (below -25 °C — with heating of the metering compartment)
Climatic design (indoor)UKhL4, -10…+40 °C
Mounting typeWall-mounted / built-in / pole-mounted
Dimensions (H×W×D), mmYaVU-1: 300×400×150; YaVU-3: 500×600×200*
Weight, kg3–15* (depending on configuration)
Operating modecontinuous
StandardsDSTU EN 61439-1/-3:2014, TU U 27.1-40132794-003:2016

*For IP54, the rated current is reduced relative to the values for IP31 — due to limited heat dissipation through the sealed enclosure. The exact value is project-specific.

*Approximate dimensions, weight, and configuration. Final parameters are agreed upon at the inquiry sheet stage. Custom designs — per the Customer's technical specification.

Standard configuration of YaVU

  • input circuit breaker for the calculated current;
  • space for an electricity meter with direct or transformer connection (DIN rail or mounting panel);
  • circuit breakers on the outgoing lines;
  • PEN/N/PE terminal block with a sealing lug;
  • set of sealing lugs for the metering compartment;
  • mounting loops / brackets for wall mounting.

Options on request

  • current transformers (CT) 100/5…1000/5 for indirect meter connection;
  • surge protection devices (SPD) class I+II;
  • 230 V service outlet in a separate compartment;
  • heating of the metering compartment for outdoor installation (below -25 °C);
  • LED compartment lighting with door switch;
  • enclosure color — RAL 7035 (light gray) standard, other RAL colors — on request.

Electricity meters

The box is supplied without a meter. The model is determined by the technical conditions of your DSO (Oblenergo). All installed meters must be certified in Ukraine and included in the DSO's register.

Lead time and warranty

Typical manufacturing time — 5–7 business days for standard models, up to 14 days for custom designs*. Warranty period — 24 months from the date of commissioning*.

*Approximate lead times and conditions. Exact lead time and warranty — as specified in the supply agreement.

Electrical diagram

Typical electrical diagram of YaVU (Ukr. ЯВУ):

Electrical diagram of YaVU

The diagram is shown for the basic design of YaVU-3 with direct-connected metering. Composition:

QF1
input automatic circuit breaker (three poles for YaVU-3, rating selected according to the calculated current)
PI
electronic active energy meter (1-phase or 3-phase, direct-connected up to 100 A or transformer-connected via CT)
QF2…QFn
automatic circuit breakers on the outgoing lines (quantity and ratings — per technical specification)
XT
PEN/N/PE terminal block with a sealing lug on the metering compartment

For transformer connection, the circuit additionally includes three current transformers (CT) with ratios of 100/5, 200/5, 400/5, 600/5, or 1000/5 — depending on the calculated current. A detailed schematic diagram for the specific design is included with the product's data sheet.

Technical specifications

Main parameters of YaVU (ЯВУ):

Parameter nameValue
Rated voltage, V230 (1-ph) / 400 (3-ph), AC
Frequency, Hz50
Grounding systemTN-C, TN-C-S (solidly grounded neutral)
Rated current (direct connection), Aup to 100
Rated current (via CT), Aup to 1000
Degree of protection (indoor)IP31 per DSTU EN 60529:2018
Degree of protection (outdoor)IP54 per DSTU EN 60529:2018
Enclosure materialPowder-coated steel / PC-ABS plastic
Climatic design (outdoor)UKhL2, -45…+40 °C
Climatic design (indoor)UKhL4, -10…+40 °C
Mounting typeWall-mounted / built-in / pole-mounted
Dimensions (H×W×D), mmYaVU-1: 300×400×150; YaVU-3: 500×600×200*
Weight, kg3-15* (depending on configuration)
Operating modecontinuous
StandardsDSTU EN 61439-1/-3:2014, TU U 27.1-40132794-003:2016

*For IP54, the rated current is reduced by 15% relative to the values specified for IP31, due to limited heat dissipation through the sealed enclosure.

*Approximate dimensions, weight, and configuration. Final parameters are agreed upon at the inquiry sheet stage. Custom designs — per the Customer's technical specification.

Versions and configuration

Standard configuration of the YaVU (ЯВУ)

  • incoming circuit breaker rated for the design current;
  • space for a direct-connected or CT-connected electricity meter (DIN rail or mounting panel);
  • circuit breakers on the outgoing lines;
  • PEN/N/PE terminal block with a sealing lug;
  • set of sealing lugs for the metering compartment;
  • mounting loops / brackets for wall-mounted installation.

Options on order:

  • current transformers (CT) 100/5…1000/5 for indirect meter connection;
  • surge protection devices (SPD) class I+II;
  • 230 V service outlet in a separate compartment;
  • heating of the metering compartment for outdoor installation (-45…-25 °C);
  • LED compartment lighting with a door switch;
  • enclosure colour — RAL 7035 (light grey) standard, other RAL colours — on order.

Electricity meters:

The enclosure is supplied without a meter. The model is determined by the technical requirements of your DSO (regional power distribution company, Oblenergo). All installed meters must be certified in Ukraine and listed in the DSO register.

Lead time and warranty:

Typical manufacturing lead time — 5-7 working days for standard models, up to 14 days for custom designs*. Warranty period — 24 months from the date of commissioning*.

*Approximate lead times and terms. The exact lead time and warranty are specified in the supply agreement.

Description and purpose

An incoming metering box (IMB) is a complete low-voltage distribution device of voltage class 0.4 kV (230/400 V, 50 Hz) for accepting the supply from the distribution system operator (DSO), commercial metering and protection of outgoing feeders. It is intended for the incoming supply point at industrial, public, utility and residential facilities. IMBs are manufactured by LK Energy Group — a switchgear manufacturer from Odesa operating since 2005: every unit ships with a data sheet, certificate and test report. The rated current and design are selected per project based on the calculated current (direct connection up to 100 A, or via current transformers up to 1000 A). Typical example: IMB-3, incoming breaker + 3-phase meter + feeder breakers. Heating for the metering compartment is added on request — for outdoor installation in cold regions.

Technical data sheet (PDF) ↓Inquiry form for sizing →

Questions & answers

FAQ

What is the rated current of the IMB?
The rated current is selected per project based on the calculated incoming current. For direct meter connection, the devices are installed directly in the power circuit; for larger loads we use transformer connection via current transformers (CTs, 100/5…1000/5). The exact rating of the incoming breaker and the CTs is determined from your technical specification and the DSO's requirements.
Can the IMB be installed on a facade / outdoors?
Yes. For outdoor and facade installation, an IP54 design per DSTU EN 60529:2018 (Ukrainian national standard, harmonized with IEC/EN) with UHL2 climatic category is ordered — protection against dust and water splashes from any direction. IP54 is not a hermetically sealed enclosure, so at this protection rating the rated current is derated with a margin for heat dissipation.
Is heating provided in the IMB?
Heating is an option, not a standard feature. A heating element is added to the metering compartment on request: for outdoor installation in cold regions (below -25 °C) or when required by the devices in the configuration. Without such a requirement, the IMB is supplied without heating.
Is the meter included in the package?
No. The box is supplied with a mounting space for the meter (DIN rail or panel) and sealing lugs, but without the meter itself. The model is determined by the technical conditions of your DSO (regional grid operator); the meter must be certified in Ukraine and listed in the DSO's register.
What documentation do you issue for the IMB?
Every IMB leaves the factory with a product data sheet, a certificate of conformity (DSTU EN 61439-3:2014, Ukrainian national standard, harmonized with IEC/EN), an acceptance test report and installation instructions. Manufacturer's technical conditions — TU U 27.1-40132794-003:2016. Warranty — 24 months.

Price request:
Incoming Metering Boxes (IMB)

Send us your single-line diagram or specification — we will estimate the configuration, lead time and price. Preliminary estimate within 24 business hours.

+380 67 104 94 91
Request a quote

Send your single-line diagram or specification to info@lk-energy.com.ua — or we will contact you and ask.

+380 67 104 94 91you can copy the numberLeave your number — we’ll call back →
+38 067 104-94-91