About the substation
KTP 10(6)/0.4 kV — reliable power supply for facilities, from the manufacturer
A complete transformer substation (KTP) 10(6)/0.4 kV is a factory-built, ready-to-use electrical installation that receives 6 or 10 kV voltage, steps it down to 0.4 kV and distributes power among consumers. KTPs are used in residential developments, agricultural and industrial facilities — everywhere reliable and safe power supply is required.
Purpose and function
The KTP is designed to receive, transform and distribute electric power. It efficiently manages power flows and ensures stable supply to the connected consumers.
Design and scope of supply
Every KTP is delivered in a complete set — with everything needed for installation and commissioning:
- Enclosure
- made of galvanized steel with anti-corrosion coating.
- Power transformer
- steps the voltage down from high to low.
- High-voltage switchgear (6/10 kV)
- incoming cubicles and switching devices (disconnectors, circuit breakers, fuses) for input, protection and control of the high-voltage section.
- Low-voltage switchgear (0.4 kV)
- LV panels, circuit breakers and fuses for control and protection of the 0.4 kV lines.
The set additionally includes operating manuals, technical documentation and spare parts.
Technical specifications
- Power transformer rating
- 160; 250; 400; 630; 1000; 1600; 2500 kVA
- Rated voltage
- HV 6 / 10 kV · LV 0.4 kV
- Rated current, HV side
- 630 A
- Rated current of LV busbars
- 400; 630; 1000; 1600; 2000; 2500; 4000 A
- HV busbar withstand
- thermal 20 kA (1 s) · electrodynamic 51 kA
- LV busbar withstand
- thermal 20 / 50 / 100 kA (1 s) · electrodynamic 50 / 110 / 220 kA
- Auxiliary circuit voltage
- AC 220 V
- Climatic design
- U3 — for installation inside unheated premises
- Maximum weight
- 6,000 kg
- Enclosure material
- Z275 galvanized steel
For KTP rated 1000 kVA and above, the HV side can be built with ShVV cabinets using vacuum circuit breakers per KSO-393-E-18V…21V main-circuit schemes.
We select the type, rating and ingress protection class according to the inquiry sheet, to match your project.
Safety and reliability
KTPs are designed by experienced engineers who account for all risks. Laboratory tests are carried out at every manufacturing stage, and before shipment each unit passes quality control (QC) — this guarantees quality, reliability and functionality.
Warranty and service life
The warranty for the KTP is 2 years (extended to 5 years by agreement); enclosure metalwork — 10 years. Design service life is 25 years. Manufacturing follows current norms and technical specifications (TU), with test reports.
Delivery
We deliver the KTP to the specified location using our own transport or via logistics companies. Self-pickup directly from the factory in Odesa is also available.
⬇ Download inquiry sheet (PDF)
More standard solutions for designers — library of standard solutions.
Find the right equipment for your site
Answer them and we will come back with a configuration and a ballpark price for your site.
Grid connection, switchgear and substations made in-house — one contractor for the entire electrical scope of your plant.
FAQ
What is a KTP?
Is a "transformer kiosk" the same as a KTP?
What does a KTP consist of?
How much does a KTP cost?
What is the difference between a KTP and a TP (transformer substation)?
Price request:
KTP 10(6)/0.4 kV
Send us your single-line diagram or specification — we will estimate the configuration, lead time and price. Preliminary estimate within 24 business hours.